GD-3134D+GD-2134L UHV Cable Sheath Fault Locator
GD-3134D UHV cable sheath fault locator
•Three fixed-point modes, suitable for different fault types.
- Step-voltage pinpointing mode: indicate the fault point directly and quickly find the fault point.
- Fault current pinpointing mode: Quickly find the fault point by measurement the resistance current in the fault cable.
- HV rod pinpointing mode: Measure the DC voltage in the fault cable to find the fault point.
• High sensitivity and large response range.
•Adopting digital signal processing technology, the signal waveform is directly displayed, and the anti-interference ability is strong.
• Automatic zero adjustment to offset the influence of ground potential changes.
•Built-in large-capacity lithium-ion battery pack, automatic shutdown under voltage, and automatic shutdown after long-term no operation.
•Solid case, light weight and portable
GD-2134L UHV cable sheath fault signal generator
•Built-in high-voltage constant current source, the output voltage and current are continuously adjustable, allowing the output to operate in a long-term short circuit.
• It has multiple safety protection functions such as grounding lockout and high-voltage zero-position start.
•It can provide a signal source for the pinpointing of the fault on the sheath of the ultra-high voltage cable.
• The transmitter can be powered by mains electricity or a generator, and the sensor and receiver can be powered by dry batteries.
GD-3134D UHV cable sheath fault locator
|
Mode |
Accessory |
Accuracy |
Max. Sensitivity |
Max. Input Range |
Display |
|
Step-Voltage Pinpoint |
Step Voltage Probe |
1%(±0.1mV) |
0.1mV |
±300V |
Signal Waveform, Fault Point Direction |
|
Fault Current Pinpoint |
Current Sensor |
1%(±1mA) |
1mA |
±1A |
Signal Waveform, Fault Current Value |
|
HV Probe Rod Pinpoint |
Step Voltage Rod |
<1%(10V-10kV) |
1V(10-1kV) 10V(1kV-10kV) |
±10kV |
DC Voltage |
|
Others |
|||||
|
Built-in |
18650 Lithium Battery, Standard 3.7V, 6.8Ah |
||||
|
Work Condition |
Temperature :-10℃-40℃; Humidity 10-90%Rh; Altitude <4500m |
||||
|
Dimension and Weight |
Dimension: 220mm×125mm×55mm; Weight: 0.9kg. |
||||
GD-2134L UHV cable sheath fault signal generator
|
Power supply |
AC 220V, can be connected to a generator (output power ≥ 1500W) |
|
Pinpoint Accuracy |
0.2m |
|
Output frequency |
1Hz |
|
Open circuit voltage |
Fundamental effective value 0~2800V,
(Pulsating DC, peak value 8kV, equivalent to the phase voltage peak value of 10kV line) |
|
Shirt circuit DC |
Effective value of fundamental wave 0~35mA
(Pulsating DC, peak100mA) |
|
Work Condition |
Temperature: -10℃-40℃; Humidity 10-90%Rh; Altitude <4500m |
|
Max. Power |
900W |
|
Dimension and Weight |
Dimension: 417mmx234mmx318mm
Weight: 16.8kg |